Welcom to Visit TingWall Inc.
A Revolution in Cutainwall Technology
 
  About TingWall
  News
  Products
  Projects
  Testing
  Technical Papers
  TingWall's Bulletins
  Affiliates
  Patents
   
   
   
   
   
   
   
CURTAIN WALL PERFORMANCES: LABORATORY VS. REAL BUILDING PDF version
Written By Raymond Ting

I. INTRODUCTION

In designing a curtain wall system, in addition to the appearance parameter, there are three major performance parameters to be considered as listed below:

1. Watertightness
2. Structural Safety
3. Energy Efficiency

In designing a new building, a building life of at least 40 years is normally considered. Therefore, it is apparent that the above three major performance parameters must be of long-term in nature. The art of devising a valid test method for evaluating a long-term performance parameter is a very complicated and challenging task, especially when one parameter is affected by the other parameter. A few examples are listed below:

1. Structural failure caused by rusting bolts and/or connection clips due to water leakage problem.
2. Significant loss of energy efficiency due to the wetting of insulation caused by water leakage problem.
3. Loss of energy efficiency due to loosening of air seal caused by structural movements.
4. Water leakage due to failure of watertightness system caused by structural movements and thus leading to the chain reactions of Item 1 and/or Item 2 above.

The main objective of conducting a mock-up test is to use the test result for predicting the long-term performance of the curtain wall on the real building. Based on this objective, the purpose of this paper is to discuss and to recommend modifications to the commonly used test methods and procedures in the industry.

II. WATERTIGHTNESS PERFORMANCE TEST

The commonly used watertightness test methods and procedures in the industry are listed below:

1 Static Water Test (ASTM E331)
2. Dynamic Water Test (AAMA 501)
3. Structural Tests
    a. ASTM E330, Negative & Positive Wind Load Test (one cycle).
    b. Vertical Interfloor Deflection Tests (3 cycles).
    c. Story Drift Tests (3 cycles).
4. Static Water Test (ASTM E331)

During each stage of the water test, if water leakage occurs, it is permissible to repair and to retest till it passes the test.

Attempting to use the short-term laboratory test for the evaluation of the long- term performance of the building would necessitate valid simulations in the aspects of natural phenomena, field workmanship, and exposure/aging effects. The laboratory results would fail to reflect the real building performance if either one of the following two conditions happens:

1. There was no water leakage in the test while water leakage happened in the real building. This has been the unsolved problem in the industry for a long, long time. Apparently, the test methods and procedures are inadequate to simulate the natural phenomena, the field workmanship, and the exposure/aging effects. Therefore, the purpose of the mock-up test has been greatly reduced to serve for devising a proper repair method.
2. There was water leakage in the test while no water leakage happened in the real building. This condition is most likely caused by wrong simulations of the natural phenomena.

The logic for the three aspects of simulations are discussed as follows:

A. Simulation of Natural Phenomena

Water leakage problem always happens on the windward wall. Therefore, the wind and the rainwater behaviors on the windward wall are logically explained below:

Amount of Water: Rainwater on the wall will accumulate as it runs down along the wall surface, therefore, the lower the level, the larger the amount of water running on the wall.

Phenomena of Wind: When the air mass in the wind impacts the wall, it must be rebound and diverted around the wall. Due to this air mass rebounding behavior, the majority of the raindrops in the air mass would be carried away from the wall surface, therefore, the stronger the wind, the lesser the amount of water on the wall. This phenomenon can be readily verified by the fact that the observed amount of running water on the wall during a dynamic water test is much lesser than that during a static water test. It is also easy to verify that the observed amount of running water on the wall of a high-rise during a rainstorm is similar to that during a dynamic water test.

Based on the above analyses of the natural phenomena, it can be concluded that the Static Water Test (ASTM E331) without the rebounding air mass behavior is only suitable to be conducted at low differential air pressure (low wind condition). This author recommends using a differential air pressure of 1.6 psf (25-mph wind) for the Static Water Test (ASTM E331). However, because almost all water leakage problems happen in strong wind condition, the Static Water Test may be eliminated if simulating the natural phenomena is the only purpose for conducting the test.

For the Dynamic Water Test (AAMA 501), AAMA recommends to use 20% of the maximum positive design wind pressure with a maximum of 12 psf as the test pressure. This is reasonable since the stronger the wind, the lesser the amount of water on the wall. However, the testing duration of 15 minutes is questionable since the duration of critical rain and wind combination during a typical rainstorm could last much longer than 15 minutes. It is recommended to extend the test duration to 60 minutes.

B. Simulation of Field Workmanship

It is well recognized that the workmanship on a test mock-up is much better than that on the real building. In most curtain wall systems, there are some critical seal locations. If poor workmanship is executed at one of the critical seal locations, it would very likely result in water leakage during the test. On the contrary, if poor workmanship is executed at a non-critical seal location, it would very likely pass the test. Therefore, simulating poor workmanship by predetermined location is not feasible. Therefore, most of the laboratory tests conducted to date failed to simulate the field workmanship and thus, supervising the field quality control becomes the major function of a curtain wall consultant.

C. Simulation of Exposure/Aging Effects

The factors causing the exposure/aging effects are stated as follows:

1. Sealant material degradation due to UV-light exposure.
2. Dislocation of sealant line or sealant adhesive failure due to stress fatigue caused by repeated cycles of structural movements. Structural movements include thermal movements, vertical inter-floor deflections, inter-floor story drifts, and wind load deflection cycles.

The commonly used structural tests on the mock-up are normally utilized as the simulation of the aging effects. However, the UV-light effect is not included and the number of structural load cycles is inadequate according to this writer's opinion. Another factor as explained below is not considered. Most curtain wall systems use curable caulking such as silicone to form the critical seals. The curable caulking is quick to form a skin while the body of the sealant normally requires a long time to solidify completely. The tests are normally conducted with the seals in the partially cured stage, which is very flexible and can tolerate high degree of displacement or distortion without breakage. Therefore, it becomes invalid to use the structural tests for the aging simulation. It is believed that story drift is more critical for sealant distortion - thus, it is more effective for aging simulation.

Summarizing from the above discussions, it is recommended to use the following procedures for conducting the water infiltration test.

1. Dynamic Water Test (AAMA 501): Use an equivalent differential air pressure of 20% of the maximum positive wind load for structural design with a maximum of 12 psf. Use a test duration of 60 minutes.
2. Structural Tests
    a. Positive and Negative Wind Loads (one cycle).
    b. Vertical Inter-floor Deflection (3 cycles).
    c. Story Drift at L/100 (50 cycles).
3. Repeat Dynamic Water Test as stated in Item 1.

The relationship between the system design principle and the proper test method is further discussed below:

1. System with Perfect Seal Principle (known as Wet Seal System): In this type of system, any imperfect seal location would become the water leakage source; therefore, the nature of the test method, static or dynamic, would have little or no effect on the test result.

2. Pressure Equalized System with Delayed Drainage: In this type of system, the intersections of the horizontal and vertical members are normally the critical seal locations. As long as the critical seals are perfect, the nature of the test method, static or dynamic, has little effect on the test result except the following conditions: Depending on the rain screen and the drainage design, the dynamic test may be more critical in causing the accumulation of water in the system. Regardless of the test method, both the test pressure and the test duration have significant effect on the outcome of the test due to the limitation of gutter capacity

3. Pressure Equalized System with Instantaneous Drainage: This type of system generally eliminates the need of critical seal and the rebounding air mass in the dynamic test is utilized to accomplish the pressure equalization. Due to the instantaneous drainage design, it is much less sensitive to the test pressure or the test duration. This system is most likely to be successful in the dynamic test. However, in the static test without the effect of the rebounding air mass, if the nozzle is located in such a way that the water is constantly spraying at the corner seam of the intersection point of the horizontal and the vertical members, with the steady suction in the static test, small amount of water could infiltrate due to the capillary action along the corner seam. If the system passed the dynamic test and failed the static test, it is very likely to create the strange situation of leakage in the test and no leakage in the real building. Due to this reason, it is recommended to use the dynamic water test only unless the static water test is conducted at a low differential air pressure.

III. STRUCTURAL TESTS

The design theory for the structural performance include the determination of forces and the limitations of material responses to the forces. Normally the determination of forces is dictated by the governing Building Code and the limitations of material responses to the forces are dictated by the industrial associations such as AISC and AAMA. These two items are separately discussed below: 1. The Determination of Forces: The forces considered in a curtain wall design include thermal load, wind load, and seismic load. The thermal load effects can normally be minimized or eliminated by design. Therefore, the consideration of thermal load in curtain wall design is normally not specified in the Building Code. The determinations of wind and seismic forces are clearly defined in the Building Codes. However, for major high-rise projects, the wind tunnel test is commonly used for more reliable wind load determination.

2. The Limitations of Material Responses to the Forces: There are three reasons for setting the limitations as discussed below:

a. Structural Safety: Several examples are stated as follows. Allowable Stresses or Safety Factors for structural components; Gap Tolerance for vertical inter-floor deflection; Strain Tolerance for inter-floor story drift. The above items can be verified by structural analyses and/or various structural test methods. However, the effects of component corrosion due to water leakage cannot be simulated. Lacking the permanent solution to the water leakage problem, the industry relies more on the corrosion resistant material such as aluminum or stainless steel.

b. Preventing Adverse Effects On Other Performance Parameter: It is well know that cycles of sealant stress and strain due to structural movements could cause sealant failure or sealant disposition. Therefore, certain limitations on deflection or displacement must be established to prevent sealant failure or sealant disposition. If the system design relies on the stiffness of the structure to minimize the sealant line strain (Case 1 Design), then, it is desirable to limit the deflection or displacement as much as economically feasible. If the system design utilizes space or releases stiffness or sealant adhesion to tolerate the component relative movements or to minimize sealant strain (Case 2 Design), then, apparently the deflection or displacement limitations can be greatly relaxed. Applying the limitations for Case 1 Design on Case 2 Design would adversely affect the performance of Case 2 Design and vice versa. For this reason, the deflection or displacement limitations should not be applied uniformly to all systems. Other type of consideration is to prevent deflection or displacement induced interference with other interior components such as ceiling and partition wall. However, this type of interference can be easily prevented by a slip joint design and no specific deflection limitation on the curtain wall is required.

c. Preventing Uneasy Feeling of Occupants: The widely used deflection limitations in the industry seem to be the product of the mixed concern of Items b and c. For example, the allowable wind load deflection for glass or aluminum plate is L/60. The allowable wind load deflection for the curtain wall frame is L/175 and sometimes with an upper limit of 3/4". The upper limit of 3/4" seems to be adopted from the floor design. It is recommended to eliminate this upper limit due to the reasons explained as follows. People walking on the floor can directly feel the floor deflection, therefore, placing an upper limit on the floor deflection is reasonable. The wind induced deflections on the curtain wall are seldom noticeable by human eyes due to the rare occurrence of extreme wind and short duration, therefore, no upper limit is necessary and in fact, the limitation of L/175 can be further relaxed unless the factor in Item b is an overriding concern.

IV. THERMAL PERFORMANCE TEST

The energy efficiency of a curtain wall system is mainly affected by the following four factors:

1. The U-Value of the vision glass.
2. The U-Value of the spandrel panel with the backside insulation.
3. The U-Value of the curtain wall supporting members.
4. The air leakage rate of the windward wall.

The above Items 1 and 2 constitute the major exposed surface area of the curtain wall, therefore, they should be considered as the dominating factor in the energy efficiency design of the curtain wall system. Normally, the exposed surface area of the curtain wall supporting members is a small percentage of the curtain wall surface, therefore, its effect on the energy should be relatively small. For Item 4 above, an allowable air leakage rate of 0.06 cfm per square foot of wall area is commonly specified in the industry. Unless massive air seal failures occur on the real building, the air leakage should have minor impact on the energy efficiency.

The thermal performance and energy efficiency can be calculated and/or tested. However, if wetting of the insulation due to water leakage occurs, the energy efficiency of the curtain wall will be significantly reduced. Since both the extent of water leakage problem and its impact on energy cannot be predicted, the long-term energy efficiency must be relied on the elimination of water leakage.

V. CONCLUSIONS

1. If the objective of a water test is to evaluate the long-term watertightness performance of the real building, then, the water test must be able to simulate the natural rainstorm phenomena, the field workmanship, and the exposure/aging effects. Based on the test methods commonly used in the industry, it is recommended to exclusively use the dynamic water test (AAMA 501) for simulating the natural phenomena of rainstorms. To simulate the effects of field workmanship and the exposure/aging factor, this writer recommends to use repeated cycles of story drift tests in addition to the normal cycles of wind load and inter-floor deflection tests. The field water test procedures (AAMA 501) should be modified in accordance to the system design principle. For a wet seal system, no modification on the stated procedures is needed. For a pressure equalized open joint system, purposely shooting a great amount of water into the joint gap is not proper since not only it can not represent the effects of natural rainstorms but also it destroys the design function of the rain screen for repelling the majority of the water from entering the joint. When the field water test is conducted in the above improper manner, water infiltration could happen due to localized overflow of water inside the joint. This would produce the strange situation of leakage in field test and no leakage in the real building. If this field test is to be applied to the open joint system, then, the nozzle should be constantly moving along the joint without complete stop at any location and without intentionally seeking for the gap.

2. In respect to the structural performance, the method of analyses and the safety factors or the stress limitations commonly used in the industry are adequate. However, to assure long-term structural performance, the stress fatigue problem and the structural component corrosion due to water leakage must be minimized. The deflection or displacement limitations for the purpose of minimizing the sealant stress or strain should be evaluated in accordance with the system design principle.

3. In respect to the energy efficiency, the U-Values of the vision panel and the spandrel panel should be the primary consideration. However, the impact of water leakage could be so significant to render the theoretical energy calculation meaningless. To encourage energy savings, giving tax incentives to buildings designed with adequate calculated energy efficiency with the assumption of no water leakage impact is not productive. It is recommended that tax incentives should be given with the combination of calculated energy efficiency and the proof of sustained long-term performance. In summary, long-term building energy performance must be relied on the elimination of water leakage problem.

*This article was published by Glass Magazine in October 2002
 
 
 
 
Other Articles
SOLUTIONS TO CURTAIN WALL PROBLEMS USING AIRLOOP SYSTEM
EVOLUTION OF CURTAIN WALL DESIGN AGAINST WATER INFILTRATION
STORY ABOUT TINGWALL SOLVING THE MOLD PROBLEM
CURTAIN WALL DESIGN AGAINST STORY DRIFT
RATING CURTAIN WALLS ON PERFORMANCE
FUNCTIONAL ISOLATION CONCEPT IN CURTAIN WALL DESIGN
CREDENTIALS OF RAYMOND TING
 
 
 
  Some of products shown may be protected by one or more of the following U.S. Patents 5,452,552; 5,596,851; 5,598,671; 5,687,524, and foreign patents based on these U.S. patents. In addition, other related patents are pending. Rights to these patents are owned by Advanced Building Systems, Inc., Wilmington, DE, a wholly-owned subsidiary of TingWall Inc.